28.3

Reset Interlocking Output (H9/C3)

All activated interlocking outputs are listed in this menu.
The output in each interlocking combination (area / point) can be manually deactivated via
this menu.
Interlocking output activated via its control expression and with latching output selected (in
EBLWin): The output has to be reset via this menu (C3).
Interlocking output activated via menu H9/C2: The output has to be reset via this menu
(C3).
Interlocking output activated via its control expression and with latching output not
selected: The output can be reset via this menu (C3).
If there are no outputs to reset,
Note: The output will be deactivated also if its control expression still is true and cannot
be activated again until after its control expression has been false again.
Action
"Access"
Scroll to menu H9.
Interlocking outputs and inputs
"A"
Activated interlocking outputs/inputs
Scroll to menu C3.
Reset interlocking output
"A"
Reset interlocking output
area 00
"A" or
Reset interlocking output
"Return"
Interlocking outputs and inputs
"Return"
--- List is empty ---
Text in display
point 00
136
Operation Manual
will be shown.
Log on to FT128 as
shown in page 35.
ACCEPT? H9
ACCEPT? C1
ACCEPT? C3
This is a list in which you
ACCEPT?
can scroll.
Press "A" (for reset) or
"Return" (no reset) to
menu C3.
Scroll or press "Return" to
ACCEPT? C3
menu H9.
Scroll or press "Return"
ACCEPT? H9