Sensitive Fault Detection Mode (H5/A2) - Panasonic Firetracker FT128 Operation Manual

Table of Contents

Advertisement

24.2

Sensitive Fault Detection Mode (H5/A2)

To increase the possibilities to detect faults during commissioning, it is possible to use the
"Sensitive fault detection mode". The time delay for each fault will then be reduced, i.e.
you might find some faults now instead of later.
The activated "Sensitive fault detection mode" is indicated by the LED Routing equipment
"Fault tx activated" and the "Fault" output for routing equipment is "activated".
Note: The "Fault" output for routing equipment is also "activated".
Action
"Access"
Scroll to menu H5
Service
Calibration of supervised outputs
"A"
Scroll to menu A2
Sensitive fault detection mode
Sensitive fault detection mode is not active
"A"
Sensitive fault detection mode is active
Sensitive fault detection mode
"Return"
"Return"
Service
Note: Don't forget to turn this mode off after commissioning.
Text in display
ACCEPT? H5
ACCEPT? A1
ACCEPT? A2
Press ACCEPT to activate
Press ACCEPT to deactivate
ACCEPT? A2
ACCEPT? H5
111
Operation Manual
FT128 Rev 2.4
Comments
Log on to FT128 as shown
in page 35.
The text shown depends
on the actual status.
Press "A" to accept or
press "Return" to menu A2.
Scroll or press "Return" to
H5.
Scroll or press "Return"