Disable All Control, Ventilation, Extinguishing Or Interlocking Outputs (H2/B4) - Panasonic Firetracker FT128 Operation Manual

Table of Contents

Advertisement

21.4
Disable All Control, Ventilation, Extinguishing or
Interlocking Outputs (H2/B4)
Outputs programmed as type Control (general), type Fire ventilation, type Extinguishing
system and type Interlocking can be collectively disabled for the type respectively (all at
the same time).
Disabled output means that even if the control expression (trigger condition) for the output
is true, the output will not be activated. Disabled outputs are shown in menu H4/U1.
The outputs will be disabled until re-enabled again (via H2/B8).
Action
"Access"
Disable or re-enable
Scroll to menu H2.
"A"
Disable zone
Disable all control, extinguishing, ventilation
Scroll to menu B4.
or interlocking outputs
"A"
Disable type:0
2=Exting
All xxxxxx outputs disabled
"0", "1", "2" or "3"
"A"
Depending on
selected type, the
following will be
shown:
"A"
Disable type: 0
2=exting 3=Interlocking
"Return"
Disable all control, ventilation, exting.
or interlocking outputs
"Return"
Disable or re-enable
Text in display
0=Control
1=Ventilation
3=Interlocking
0=control 1=ventilation
91
Operation Manual
Log on to FT128 as shown
in page 35.
ACCEPT? H2
ACCEPT? B1
ACCEPT? B4
Press:
"0"=control outputs
ACCEPT?
"1"= ventilation outputs
"2"= extinguishing output
"3"=interlocking outputs.
Press "A" to accept. LED
(L8) "Disablement" will
illuminate
XXXXX=control,
ventilation, extinguishing or
interlocking.
If more disablements
ACCEPT?
required, continue as
above otherwise, press
"Return" to menu B4.
Scroll or press "Return" to
ACCEPT? B4
menu H2.
Scroll or press "Return"
ACCEPT? H2
FT128 Rev 2.4