Reset Activated Output (H8/S10) - Panasonic Firetracker FT128 Operation Manual

Table of Contents

Advertisement

27.10

Reset activated output (H8/S10)

Output(s) activated via menu H8/S9 have to be reset via this menu (H8/S10).
Note: Only output types that are activated will be shown and possible to select.
Action
Text in display
"Access"
Scroll to menu H8.
Maintenance
"A"
Acknowledge SERVICE signal
Scroll to menu S10
Reset activated output
"A"
Reset output type: 0
0=Loopunit 1=S 2=R0 3=EXPB
Depending on if 0, 1,
Reset output: 0, technical address 000
2 or 3 is selected
one of the
Reset S0
alternatives will be
shown.
Reset R0
Reset output: 0, expansion board 0
"A"
Reset output type: 0
0=Loop unit
"Return"
Reset activated output
"Return"
Maintenance
1=S 2=R0 3=EXPB
133
Operation Manual
Comments
Log on to FT128 as
shown in page 35.
ACCEPT? H8
ACCEPT? S1
ACCEPT? S10
Only output types that
are activated will be
ACCEPT?
shown. Loop unit=3361
or 3364
S=S0-S1
R0=R0
EXPB= 4581 or 4583
L=A list in which you
can scroll. Select the
ACCEPT? L
output to reset and
press "A".
ACCEPT? L
ACCEPT? L
ACCEPT? L
Only output types that
are activated will be
ACCEPT?
shown.
When all outputs are
reset,
--- List is empty ---
be shown.
Scroll or press "Return"
to menu H8.
ACCEPT? S10
Scroll or press "Return".
ACCEPT? H8
FT128 Rev 2.4