Alarm References - Huawei FusionModule800 Maintenance Manual

Smart small data center
Hide thumbs Also See for FusionModule800:
Table of Contents

Advertisement

FusionModule800 Smart Small Data Center
Maintenance Guide
This section provides only measures to clear the Smart Module major and critical alarms. For details
about other alarms, download them from the ECC800 WebUI.
Table 3-1 Alarm list
Component
Surge
protective
device (SPD)
Automatic
transfer switch
(ATS)
Issue 02 (2016-11-15)
3
Alarm Name
Alarm
Severity
SPD fault
Major
ATS No
Major
Voltage (alarm
1 on the
display)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.

3 Alarm References

Alarm References
Possible
Cause
A surge
protection
module is
damaged or the
SPD circuit
breaker has
tripped.
The ATS
upstream
switch is not
turned on.
The
controller
power cable
is not
connected.
The input
power cable
is loose or
not
connected.
Measures
Replace the
surge protection
module or
switch on the
SPD circuit
breaker.
1. Check that
the upstream
switch is
turned on.
2. Check that
the
controller
power cable
is securely
connected.
3. Check that
the input
power cable
is properly
connected.