Figure 5-43 Position of the filter dryer
(1) Filter dryer
Step 6 Weld the new filter dryer to the pipe.
Step 7 Secure the new filter dryer using cable ties.
Step 8 Perform a leakage test with nitrogen again.
Step 9 After checking that the air conditioner does not leak, vacuumize the air conditioner and
charge refrigerant.
Step 10 Reinstall the left front panel and left rear panel.
----End

5.3.2.4 Replacing a High Pressure Sensor

Prerequisites
Context
Issue 02 (2016-11-15)
A high pressure sensor needs to be replaced.
A spare high pressure sensor of the same model is available and functional.
Tools: Phillips screwdriver, refrigerant retrieval device (required based on local
conditions), nitrogen injection and pressure preservation tool, vacuumization tool,
refrigerant injection tool, adjustable wrench, and sealant.
Preparation: Power off the outdoor unit.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
(2) Welding point