FusionModule800 Smart Small Data Center
Maintenance Guide
Component
Issue 02 (2016-11-15)
Alarm Name
Alarm
Severity
Hot-aisle HT
Critical
Comp drive
Critical
comm failed
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Alarm References
Possible
Measures
Cause
1. The
1. Adjust the
installation
installation
position of
position of
the T/H
the T/H
sensor is
sensor.
improper.
2. Measure the
2. The ambient
ambient
temperature
temperature.
exceeds the
3. Adjust the
upper
hot aisle
threshold.
high
3. The hot aisle
temperature
high
alarm
temperature
threshold.
alarm
4. Maintain or
threshold is
replace the
inappropriat
T/H sensor.
e.
5. Add air
4. The
conditioners
temperature
.
and
humidity
displayed on
the LCD is
different
from the
actual
temperature
and
humidity.
5. The thermal
load power
is high or
the cooling
capacity is
insufficient.
1. The
1. Check cable
compressor
connections
drive cable
to the
connection
compressor
is faulty.
drive.
2. The
2. Maintain or
compressor
replace the
drive is
compressor
faulty.
drive.
3. The
3. Switch on
compressor
the
drive circuit
compressor
breaker is
drive circuit
off.
breaker.