FusionModule800 Smart Small Data Center
Maintenance Guide
0104 in NetCol5000-A0104 is variable and subject to changes with the air conditioner connection
sequence. The displayed value prevails.
Step 2 Disconnect the power supply from the air conditioner control unit after the air conditioner
shuts down over the EMS.
Step 3 Remove the return air filter by referring to
Step 4 Remove the top metal sheet of the condensate pump, as shown in
Figure 5-29 Removing a condensate pump
Step 5 Remove the hose clamps at the water inlet and outlet hoses of the condensate pump using a
Phillips screwdriver, remove the hoses and take out the pump, as shown in
Step 6 Install the new condensate pump in the original position by performing the preceding steps in
reverse order, connect the hoses, and install hose clamps.
Step 7 Clear up the condensate pump total running time.
Issue 02 (2016-11-15)
b.
Tap the cabinet that houses the air conditioner in the micro-module view.
c.
Tap the air conditioner to be set in the cabinet layout diagram.
d.
Choose Real-time Data > OFF.
Method 2: Log in to the ECC800 WebUI as admin. Choose Monitoring > Air
Conditioner > NetCol5000-A0104 > Controls > Ctrl Info, set On/off status on
EMS > Off, and then click Submit.
Method 1: Log in to the ECC800 mobile phone or pad app as admin.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5.3.1.1 Replacing a Return Air
Figure
5 Parts Replacement
Filter.
5-29.
Figure
5-29.
64