Step 7 Weld from the two welding points shown by (1) and (5) in
pipe that connects the compressor to the oil separator, and then remove the suction pipe.
To avoid burning the internal components, other pipes, thermal insulation foam, power cables,
and labels, take protective measures, such as spreading wet cloth, around the welding
position.
Step 8 Remove the three nuts (shown by [3] in
mm socket wrench, and remove the compressor.
Figure 5-42 Compressor position
(1) Welding point for the
suction pipe
(4) Oil separator
Step 9 Remove the rubber plugs from the suction and discharge pipes of the new compressor, and
screw the new compressor bound with an oil heating belt to the base using a 13 mm socket
wrench.
Issue 02 (2016-11-15)
(2) Compressor
(5) Welding point for the
discharge pipe
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
Figure
5-42) from the compressor base using a 13
5 Parts Replacement
5-42. Remove the discharge
(3) Nuts on the
compressor base
81