FusionModule2000 Smart Modular Data Center
Maintenance Guide
Item
Smoke detector
availability

2.5.2 Routine Maintenance for the Alarm Beacon

Table 2-15 Routine maintenance for the alarm beacon
Item
Issue 01 (2016-10-18)
Maintenance
Interval
Semi-annually
You are advised to clean the smoke detectors every two years.
Maintenance
Interval
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Method
Expected
Result
Use a dedicated
If the smoke
test instrument
density is
or a smoke
below the
generator to test
alarm
the smoke
threshold,
detector. Blow
the alarm
smoke to the
indicator
smoke detector
blinks once
probe and
every 6
observe the
seconds.
indicator status.
If the smoke
density
exceeds the
alarm
threshold,
the alarm
indicator is
steady on.
Method
Expected
Result
2 Routine Maintenance
Exception
Handling
If the smoke
density is
below the
alarm
threshold
but the
alarm
indicator
blinks twice
every 6
seconds, the
smoke
detector is
faulty.
Replace the
smoke
detector.
If the smoke
density
exceeds the
alarm
threshold
but the
alarm
indicator is
not steady
on, replace
the smoke
detector.
Exception
Handling
13