Advertisement

FusionModule800 Smart Small Data Center
Maintenance Guide
Component
Issue 02 (2016-11-15)
Alarm Name
Alarm
Severity
Full water
Critical
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Alarm References
Possible
Measures
Cause
1. The cables
1. Check the
to the high
cables to the
liquid level
high liquid
detector are
level
not
detector.
connected
2. Maintain or
properly.
replace the
2. The high
high liquid
liquid level
level
detector is
detector.
faulty.
3. Maintain or
3. If a
replace the
condensate
condensate
pump is
pump.
configured,
4. Clear the
the
obstacles in
condensate
the
pump may
condensate
be faulty, or
pump.
the
5. Clear the
condensate
foreign
pump
matter at the
draining
automatic
capacity
drainage
declines.
port or in
4. If a
the internal
condensate
drainpipe.
pump is
configured,
the
condensate
pump
drainpipe
may be
blocked.
5. If no
condensate
pump is
configured,
maybe the
automatic
drainage
port is
blocked, an
internal
drainpipe is
blocked, or
a drainpipe
is frozen.