FusionModule800 Smart Small Data Center
Maintenance Guide
Yearly preventive maintenance table
Table A-3 Yearly preventive maintenance table
Maintenance area
Power Distribution
System
Issue 02 (2016-11-15)
Item
Power indicators
Surge protection
module
Emergency fan
Dust inside the
power distribution
subrack
Bolts between power
cables and the
busbar after
power-off
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Operation
Expected Result
Check the
All indicators are
indicators.
normal.
Check the surge
protection module
indicator and
miniature circuit
breaker (MCB)
status.
Check whether the
The top of the fan
top of the
is clean and not
emergency fan is
blocked.
blocked.
Check whether
The white paper
there is dust on the
that you use to
power distribution
wipe the cabinet
subrack panel.
panel is clean.
Tighten all bolts
The bolts are
regularly using an
secured.
adjustable wrench.
A Preventive Maintenance Table
Troubleshootin
g
The power supply
is normal. Replace
the indicator that
generates no or
dim light.
The surge
If the surge
protection
protection
module
module
indicator is
indicator is
steady green.
steady red,
replace the
The MCB is
surge
ON.
protection
module.
If the MCB is
OFF, switch it
on.
Clean dust and
foreign matters
from the top of the
fan.
If the white paper
is dirty, clean the
power distribution
subrack.
Tighten a bolt if it
is loose.
133