FusionModule800 Smart Small Data Center
Maintenance Guide
Component
Intelligent
battery
monitoring
system
Issue 02 (2016-11-15)
Alarm Name
Alarm
Severity
Inverter fault
Critical
Communication
Critical
Failure
BCB Tripping
Critical
Single Batt.
Critical
terminal off
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Alarm References
Possible
Measures
Cause
The inverter
Eliminate the
output
short circuit at
short-circuits.
the output port
cable
connection, and
then power on
and start the
inverter again.
If the fault
persists, contact
Huawei
technical
support.
The network
Check the cable
cable
connection to
communication
the smart ETH
is interrupted.
gateway.
The battery
Identify the
has
alarm cause,
discharged
rectify the fault,
to the
and switch on
end-of-disch
the BCB box.
arge (EOD)
threshold.
The battery
circuit
breaker
(BCB) box
is manually
disconnecte
d.
There is a
security risk
in the
battery loop.
A battery
Check that
terminal
battery
screw is not
terminal
tightened.
screws are
tightened.
The battery
terminal is
Check that
not properly
battery
connected to
terminals
the
are properly
connector.
connected to
connectors.