FusionModule800 Smart Small Data Center
Maintenance Guide
Component
UPS
Issue 02 (2016-11-15)
Alarm Name
Alarm
Severity
Rectifier fault
Critical
Internal fault
Critical
Fan fault
Critical
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Alarm References
Possible
Measures
Cause
The mains
Rectify the
has
fault, and
experienced
power on
a transient
the UPS
high
again.
voltage.
Check that
The output
the load
carries
types are
special loads
supported
such as the
by the UPS.
inductive
Enable the
and
transformer
rectification
mode.
loads.
Contact
The output
Huawei
carries the
technical
transformer
support.
load but the
transformer
mode is not
enabled.
The
hardware is
damaged.
The bypass
Correct the
input cable
bypass input
connection does
cable
not match the
connection so
output system.
that it matches
the output
system.
The fan is
Clean up
abnormal.
foreign matter
around the fan.
If the fault
persists, contact
Huawei
technical
support.