Component
Issue 02 (2016-11-15)
Alarm Name
Alarm
Severity
Comp drive
Critical
short period
Indoor fan
Critical
failure
EEV high
Critical
overheating
locked
EEV auto
Critical
control fault
Indoor fan
Critical
malfunction in
high humidity
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Alarm References
Possible
Measures
Cause
A compressor
Maintain or
drive fault
replace the
occurs multiple
compressor
times or the
drive, and clear
compressor
the cumulative
drive fault is
runtime.
not rectified
within a long
time.
1. The indoor
1. Maintain or
fan is faulty.
replace the
indoor fan.
2. Cables to
the indoor
2. Check
fan are loose
cables to the
or damaged.
indoor fan.
1. The
1. Reinstall the
electronic
electronic
expansion
expansion
valve coil is
valve coil.
loose.
2. Replace the
2. The
electronic
electronic
expansion
expansion
valve coil.
valve coil is
3. Replace the
faulty.
electronic
3. The
expansion
electronic
valve.
expansion
valve is
faulty.
1. The suction
1. Rectify the
pressure
fault of the
sensor is
suction
faulty.
pressure
sensor.
2. The suction
temperature
2. Rectify the
sensor is
fault of the
faulty.
suction
temperature
sensor.
One or more
Check and
indoor fans are
replace faulty
indoor fans.
faulty and the
ambient
humidity is
high.
15