Huawei FusionModule800 Maintenance Manual page 148

Smart small data center
Hide thumbs Also See for FusionModule800:
Table of Contents

Advertisement

FusionModule800 Smart Small Data Center
Maintenance Guide
Maintenance area
The Water Sensor
and Water Detection
Rope
The Structural
System
The Cooling System
Issue 02 (2016-11-15)
Item
Cleanliness
Battery connection
Ambient temperature
of the intelligent
battery monitoring
system
Water sensor and
water detection rope
function
Glass door steel
glass cleaning
Water pan filter
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Operation
Expected Result
N/A
Wipe the battery
surface using a
piece of white
paper and the paper
does not turn black.
N/A
Battery terminals
and cables are in
good contact.
N/A
The ambient
temperature of the
intelligent battery
monitoring system
is lower than 45° C.
Place the water
A water leakage
detection rope into
alarm is generated.
the water and check
whether a water
leakage alarm is
generated by the
water sensor.
Use a soft cotton
N/A
cloth to clean the
glass.
Clean the glass
with clean water.
Do not use any
organic solvent
such as alcohol,
thinner, or glass
cleaner.
To avoid
scratching, do
not use
excessive force
when cleaning
the glass.
N/A
Check that the
water pan filter is
clean and not
blocked.
A Preventive Maintenance Table
Troubleshootin
g
Remove dust from
the battery
surface.
Ensure that battery
terminals and
cables are in good
contact.
Find the cause of
an abnormal
temperature.
If no water
leakage alarm is
generated, replace
the water
detection rope by
referring to
Replacing a Water
Sensor and Water
Detection
Rope.
N/A
Clean it with
water.
5.4.15
142