FusionModule800 Smart Small Data Center
Maintenance Guide
Quarterly preventive maintenance table
Table A-2 Quarterly preventive maintenance table
Maintenance area
Power Distribution
System
UPS
Issue 02 (2016-11-15)
Item
Power indicators
Surge protection
module
Emergency fan
Operating
environment
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Operation
Expected Result
Check the
All indicators are
indicators.
normal.
Check the surge
protection module
indicator and
miniature circuit
breaker (MCB)
status.
Check whether the
The top of the fan
top of the
is clean and not
emergency fan is
blocked.
blocked.
N/A
A Preventive Maintenance Table
Troubleshootin
g
The power supply
is normal. Replace
the indicator that
generates no or
dim light.
The surge
If the surge
protection
protection
module
module
indicator is
indicator is
steady green.
steady red,
replace the
The MCB is
surge
ON.
protection
module.
If the MCB is
OFF, switch it
on.
Clean dust and
foreign matters
from the top of the
fan.
Ambient
If the humidity
temperature:
and
0–40° C
temperature are
abnormal,
Humidity:
check the air
0–95% RH
conditioner
(non-condensin
status.
g)
If the input
voltage is
abnormal,
check the
power grid
status and input
cable
connection.