Replacing An Outdoor Fan - Huawei FusionModule800 Maintenance Manual

Smart small data center
Hide thumbs Also See for FusionModule800:
Table of Contents

Advertisement

FusionModule800 Smart Small Data Center
Maintenance Guide
Table 5-1 Total refrigerant amount
Type
One-way pipe length (m)
Total refrigerant amount
(kg)
Figure 5-39
Figure 5-39 Outdoor unit components
(1) Outdoor fan blade
(4) Low pressure switch
(7) Oil heating belt

5.3.2.1 Replacing an Outdoor Fan

Prerequisites
Context
Issue 02 (2016-11-15)
shows the components of an outdoor unit.
An outdoor fan needs to be replaced.
A spare outdoor fan of the same model is available and functional.
Tools: Phillips screwdriver, small wrench, cable tie, diagonal pliers.
Preparation: Power off the outdoor unit.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
NetCol5000-A010
0 < L ≤ 30
6
(2) Safety valve
(5) Low pressure sensor
5 Parts Replacement
30 < L ≤ 60
6 + (L – 30) x 0.05
(3) High pressure switch
(6) Compressor
77

Advertisement

Table of Contents
loading

Table of Contents