Replacing An Electric Heater - Huawei FusionModule800 Maintenance Manual

Smart small data center
Hide thumbs Also See for FusionModule800:
Table of Contents

Advertisement

FusionModule800 Smart Small Data Center
Maintenance Guide
Figure 5-31 Removing a wet film humidifier
Step 7 Install the new wet film humidifier in the original position by performing the preceding steps
in reverse order, and connect the hose.
Step 8 Clear up the wet film humidifier total runtime.
Step 9 After starting the air conditioner and ensuring that the water inlet pipe properly connects to
the wet film humidifier. Log in to the ECC800 WebUI as admin. Choose Monitoring > Air
Conditioner > NetCol5000-A0104 > Running Parameters > System Controls > Ctrl Info,
choose Humid > Enable, and the click Submit.
----End

5.3.1.6 Replacing an Electric Heater

Prerequisites
Issue 02 (2016-11-15)
Method 1: Log in to the ECC800 mobile phone or pad app as admin.
a.
Choose Home.
b.
Tap the cabinet that houses the air conditioner in the micro-module view.
c.
Tap the air conditioner to be set in the cabinet layout diagram.
d.
Choose Real-time Data > Perf Maint, clear up the wet film humidifier total
running time.
Method 2: Log in to the ECC800 WebUI as admin. Choose Monitoring > Air
Conditioner > NetCol5000-A0104 > Controls > Performance Maint Ctrl, clear up the
wet film humidifier total running time.
Tools: Phillips screwdriver, diagonal pliers or scissors.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Parts Replacement
68