FusionModule800 Smart Small Data Center
Maintenance Guide
Component
Issue 02 (2016-11-15)
Alarm Name
Alarm
Severity
ATS Low
Major
Voltage (alarm
2 on the
display)
ATS
Major
Overvoltage
(alarm 3 on the
display)
ATS Open
Major
Phase (alarm 4
on the display)
ATS
Major
Three-Phase
Voltage
Imbalance
(alarm 5 on the
display)
ATS Incorrect
Major
Phase Sequence
(alarm 6 on the
display)
Abnormal ATS
Major
Frequency
(alarm 7 on the
display)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Alarm References
Possible
Measures
Cause
1. Switch to
The mains
the backup
voltage is
power
low.
supply.
ATS
2. Ensure that
parameters
ATS
are not set
parameters
properly.
are set
properly.
1. Switch to
The mains
the backup
voltage is
power
high.
supply.
ATS
2. Ensure that
parameters
ATS
are not set
parameters
properly.
are set
properly.
The input
Check that the
power cable is
input power
loose or not
cable is
connected.
properly
connected.
The mains is of
Rectify the
poor quality.
mains.
The phase
Check that the
sequence of the
input power
input power
cable is
cable is
properly
incorrect.
connected.
The mains is of
Rectify the
poor quality.
mains.