Huawei FusionModule800 Maintenance Manual page 15

Smart small data center
Hide thumbs Also See for FusionModule800:
Table of Contents

Advertisement

FusionModule800 Smart Small Data Center
Maintenance Guide
Component
Issue 02 (2016-11-15)
Alarm Name
Alarm
Severity
Single Batt.
Critical
Exception
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Alarm References
Possible
Measures
Cause
The battery
Check
shell is
whether the
broken,
appearances
resulting in
of abnormal
electrolyte
batteries are
and
intact, and
electricity
replace
leakage.
abnormal
batteries.
The battery
loop cable is
Check
broken and
whether
short-circuit
battery loop
ed to the
cables are
ground,
deteriorated
resulting in
or broken,
electricity
and replace
leakage.
faulty
cables.