FusionModule800 Smart Small Data Center
Maintenance Guide
Component
Issue 02 (2016-11-15)
Alarm Name
Alarm
Severity
Ambient high
Critical
temperature
alarm
EEV driver
Critical
power off
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Alarm References
Possible
Measures
Cause
1. The ambient
1. Measure the
temperature
ambient
is higher
temperature.
than the
2. Install an
upper
awning.
threshold.
3. Calibrate or
2. There is
replace the
strong
temperature
radiation on
sensor.
the
monitoring
point,
resulting in
high
temperature.
3. The
temperature
displayed on
the LCD is
different
from the
actual
temperature.
The electronic
Replace the
expansion valve
main control
drive is faulty.
module.