Huawei FusionModule800 Maintenance Manual page 124

Smart small data center
Hide thumbs Also See for FusionModule800:
Table of Contents

Advertisement

FusionModule800 Smart Small Data Center
Maintenance Guide
Maintenance area
Camera
The Intelligent
Battery Monitoring
System
Issue 02 (2016-11-15)
Item
Operating
environment
Cable connections
Camera availability
Battery management
alarm
Cleanliness
Battery connection
Ambient temperature
of the intelligent
battery monitoring
system
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Operation
Expected Result
N/A
N/A
The cable
connections are
secure.
N/A
Cables are not
damaged.
On the ECC800
The monitoring
WebUI, click
page is properly
Maintenance >
displayed after you
View Video >
click View.
Video Info to enter
the video view
page. Type the
camera name or IP
address to find the
camera, and click
View to view the
real-time
monitoring page.
N/A
No battery
management alarm
is generated.
N/A
Wipe the battery
surface using a
piece of white
paper and the paper
does not turn black.
N/A
Battery terminals
and cables are in
good contact.
N/A
The ambient
temperature of the
intelligent battery
monitoring system
is lower than 45° C.
A Preventive Maintenance Table
Troubleshootin
g
Ambient
If the humidity or
temperature:
temperature is
–20° C to +65° C
abnormal, check
the air conditioner
Humidity:
status.
0–95% RH
(non-condensin
g)
Secure loose
cables.
Replace damaged
cables.
If the monitoring
page is not
displayed after
you click View,
check that the IP
address is
correctly set, and
check cable
connection or
replace the
camera. For
details, see
Replacing a
Camera.
Find the cause of
an alarm based on
the alarm
information.
Remove dust from
the battery
surface.
Ensure that battery
terminals and
cables are in good
contact.
Find the cause of
an abnormal
temperature.
5.4.10
118