FusionModule800 Smart Small Data Center
Maintenance Guide
Figure 5-74 Connecting a conversion cable to a water detector
Step 2 Replace a water detection rope.
1.
2.
Figure 5-75 Connecting a new water detection rope
(1) Conversion cable end B, connecting to
the water detection rope
----End
Follow-up Procedure
Check whether the new water detector works properly. Connect the network cable between
the water detector and ECC800, immerse the water detection cable in water, and check
whether an alarm is generated. If an alarm is generated, the replacement is complete.
Issue 02 (2016-11-15)
Remove the faulty water detection rope from the port.
Install a new water detection rope, as shown in
The water detection rope and conversion cable are interconnected through the male and female
connectors.