Replacing A Condensate Pump - Huawei FusionModule800 Maintenance Manual

Smart small data center
Hide thumbs Also See for FusionModule800:
Table of Contents

Advertisement

FusionModule800 Smart Small Data Center
Maintenance Guide
Figure 5-28 Removing a fan
Step 8 Install the new fan in the original position by performing the preceding steps in reverse order,
and insert the fan terminal.
Step 9 Clear up the indoor fan total runtime.
----End

5.3.1.3 Replacing a Condensate Pump

Prerequisites
Context
The condensate pump is maintained from the rear.
Procedure
Step 1 Shut down the air conditioner over the EMS.
Issue 02 (2016-11-15)
Method 1: Log in to the ECC800 mobile phone or pad app as admin.
a.
Choose Home.
b.
Tap the cabinet that houses the air conditioner in the micro-module view.
c.
Tap the air conditioner to be set in the cabinet layout diagram.
d.
Choose Real-time Data > Perf Maint, clear up the indoor fan total runtime.
Method 2: Log in to the ECC800 WebUI as admin. Choose Monitoring > Air
Conditioner > NetCol5000-A0104 > Controls > Performance Maint Ctrl, clear up the
indoor fan total runtime.
Tool: Phillips screwdriver.
A condensate pump needs to be replaced.
A spare condensate pump of the same model is available and functional.
Method 1: Log in to the ECC800 mobile phone or pad app as admin.
a.
Choose Home.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Parts Replacement
63