Xedge Chassis Systems

Xedge 6640/6645 Chassis

Xedge 6640 and 6645 are 16-slot chassis that allows full redundancy by employing main and
standby slot-0 controllers, main and standby switch fabric, and backup power supplies. Both chassis
models also accommodate a Fan Tray Assembly and Network Timing Modules (NTM).
CAUTION
Do not block the openings on the top and bottom of the chassis.
CAUTION
below each chassis for adequate ventilation as described in the paragraphs below.
CAUTION
Do not install power modules in the chassis until the chassis is properly mounted int the cabinet.
CAUTION
chassis requires two people. Before moving the chassis, take all necessary precautions to prevent
equipment damage and avoid personal injury. Be sure to disconnect all cables.

Xedge 6640/6645 Technical Specifications

The Xedge 6640/6645 chassis obtain power from one or two power feeds and up to four power
supplies for full power redundancy. The Xedge 6640 is an AC-powered chassis that employs GPS-
14 AC supplies; the Xedge 6640 is a DC-powered chassis that employs DPS-14 DC supplies.
The installation and operation information in this section applies to both the Xedge 6640 and 6645
chassis, except where noted.
For detailed Xedge 6640 specifications, refer to
For detailed Xedge 6645 specifications, refer to
Table 2-7
Xedge 6640 Technical Specifications
Xedge 6640 AC Chassis (P/N 010B197-001), GPS-14 AC Power Supply (035P114-001)
Input Voltage (Nominal)
Input Frequency
Input Current
Service Current Requirement
Maximum Consumption
Fuse Rating
Heat Dissipation
Dimensions (H x W x D)
Weight
Temperature, operating
Temperature, non-operating
Humidity
Altitude, operating
Altitude, non-operating
Compliance
Note
1. The Xedge 6640 chassis comes with two North American line cords. Non-US line cords are optional.
2. At 100VAC, the maximum output current must not exceed 140A to comply with safety requirements.
032R440-000
Issue 17
When installing two chassis in the same cabinet or open rack, provide space above and
A fully loaded chassis weighs approximately 130 pounds (59 Kg). Lifting a fully loaded
90-132VAC
47-63 Hz
16A (See Note 2 below.)
20A
1300 W (with two power supplies)
12A / 250V
4,600 BTU/hr maximum
24.5 in (62.2 cm) x 19.0 in (48.3 cm) x 16.6 in (42.2 cm)
130 lbs (59 kg), fully loaded
32 to 122 deg. F (0 to 50 deg. C)
-40 to 158 deg. F (-40 to 70 deg. C)
Up to 95% without condensation
0 to 10,000 ft (0 to 3,047 m)
0 to 40,000 ft (0 to 12,191 m)
CISPR 22 Class A; UL recognized (UL1459);
c-UL recognized (CSA C22.2 #225); TUV licensed (EN60950); CE Mark
Xedge 6000 Hardware
Installation & Setup Guide
Xedge 6640/6645 Chassis
Table
2-7.
Table
2-8.
198-264VAC (See Note 1 below.)
47-63 Hz
8A
10A
2-27