Xedge 6160 Connections - General DataComm Xedge 6000 Series Hardware Installation

Table of Contents

Advertisement

Xedge Chassis Systems

Xedge 6160 Connections

The Xedge 6160 rear panel provides connectors for power sources, management, grounding and
alarm connections. The following paragraphs describe how to make these connections.
AC Power Connections
The AC power source should not be under switch control. If the Xedge 6160 is connected to other
equipment, it should be powered by the same AC source as that equipment to prevent large
circulating currents induced by differences in ground potential. If it is impossible to determine
whether the equipment is powered by the same AC source, verify that a potential difference of less
than 0.25 V rms exists between the grounding circuits of the respective power outlets.
Each Xedge 6160 AC chassis is equipped with one AC power cord (US 120 VAC). Export power
cords are optional. Plug the appropriate end into the AC receptacle of the power input module and
plug the other end into a polarized outlet that provides the required AC power.
The following table provides ordering information for optional AC power cords:
AC Power Cord for:
Australia, New Zealand, China
Europe
Italy
Japan
North American (US)
Switzerland
Taiwan, Philippines
UK, Ireland
DC Chassis Power Connections
To connect an Xedge 6160 chassis to a DC power source the following customer-provided
components are required:
Station battery source(s)
Voltage measured at the field terminal connector must not be less than -42Vdc.
Insulated copper wire sized to carry 15A at -48Vdc nominal.
EMC Requirements
To comply with EMC requirements, the wire pair between the power distribution point and the
chassis cabinet must have at least one twist per inch. If the distribution point and chassis are
separated by 5 feet or more, the twisted wire must extend at least 5 feet from the chassis. The twisted
pair wiring must incorporate a shielding braid (Alpha Wire Corporation number 2172, or
equivalent). The shields braid must be electrically connected to the chassis GND at both ends, at the
DC mains entry terminal block GND terminal, and at a clamp bonded to the chassis metal.
Note
For contact information see Alpha Wire Corporation's website at www.alphawire.com.
2-14
Part Number
830-002-010
830-061-002
830-002-008
830-002-009
830-068-001
830-061-003
830-002-011
830-060-102
Xedge 6000 Hardware
Installation & Setup Guide
Xedge 6160 Chassis
032R440-000
Issue 17