Detailed commissioning steps
15
Read in devices on detector line
15.13 Read in devices on detector line
15.14 Detaching the device
82 | 178
Building Technologies
Fire Safety
NOTICE
Incorrect order for reading in a loop
Error when reading in a loop.
The C-NET detector lines are detected as stubs during the first system start-up,
e.g., 'Line' 11, 'Line' 12 (2-digit line number), even if they are connected as a loop.
●
For loop with line separator: Switch the second 'Line' or 'Line' 12 off.
●
To read in a loop, always select the first 'Line', in this case 'Line' 11. 'Line' 12
is then read in automatically.
A loop is displayed with a 1-digit line number, in this case as 'Line' 1 once it
has been read in.
●
Proceed in the same way from 'Line' 21/22 (loop 2) to 'Line' 41/42 (loop 4).
w For ↑ loop with line separator: The second 'Line' is switched off. Link [➙ 79]
1. In the main menu, select 'Topology' > ↑ 'Hardware tree' > ↑ 'Station' > ↑ line
card > ↑ detector line.
2. Press the 'More Options' ↑ softkey and select 'Execute commands'.
3. Select the 'Read in installed devices' command.
a The C-NET devices are read in.
a The following message is shown following successful reading in:
'Command executed'
If you want to permanently remove a device, uninstall the device – and, if
necessary, the base – and connect the wires of the detector line.
You will find more information about installing and uninstalling in the
documentation for the corresponding device.