Entering Network Settings - Siemens FS720 Commissioning, Maintenance, Troubleshooting

Fire detection system
Table of Contents

Advertisement

18.3 Entering network settings

Building Technologies
Fire Safety
w The network topology is known.
w 'Advanced Mode' is selected.
Enter the network settings in the following order:
l
External IP address 'IP Address ext.'
Routing mode 'Routing Mode'
Router network data 'Router'
Load the network settings to FN2009-A1.
Entering external IP address, 'IP Address ext.'
1. Double-click on the field below the 'IP Address ext.' designation.
a The external IP address for the FN2009-A1 can be edited.
2. Enter the following IP address: 10.169.29.80.
Entering routing mode, 'Routing Mode'
The following settings apply for the planned network access to ↑ GAP with
activated DHCP server.
'192.168.201.X' must be changed accordingly for network access to the standby
router or with IP address details.
w 'Module 1' is highlighted in the 'View' window.
1. Press <F4> on the keyboard or open the 'Edit' > 'Properties' menu.
a The 'Module Properties' window is displayed:
Commissioning security module (firewall) FN2009-A1
Entering network settings
A6V10210416_j_en_--
2018-08-29
18