Correcting Swapped Devices - Siemens FS720 Commissioning, Maintenance, Troubleshooting

Fire detection system
Table of Contents

Advertisement

Repair
24

Correcting swapped devices

24.6 Correcting swapped devices
158 | 178
Building Technologies
Fire Safety
When non-stationary C-NET devices have been swapped over in their bases, e.g.,
while work is carried out, the 'Line' is not fault-free.
The following message is shown on the display of the ↑ Person Machine Interface
for each C-NET device that has been swapped over:
'Zone', 'Serial no. ("ID-Nr.")', 'Device missing'
If the C-NET detector line was restarted, the following message is displayed for
each swapped C-NET device:
'Zone', 'Serial no. ("ID-Nr.")', 'Dev.location fault'
Troubleshooting
'Faults' of C-NET devices of the same type that have been swapped over can
then be rectified using the Person Machine Interface without having to find the
original base.
w The device types in the corresponding bases are correct.
1. Rectify localization errors. Link [➙ 86]
2. Connect the PC to the 'Station'. Link [➙ 27]
3. Load the configuration from the 'Station' to the PC.
4. Disconnect the PC from the 'Station'. Link [➙ 27]
A6V10210416_j_en_--
2018-08-29