Detailed commissioning steps
15

Converting a standalone station to a networked station

15.7 Converting a standalone station to a networked
78 | 178
Building Technologies
Fire Safety
station
NOTICE
Configuring IP addresses manually
Once a standalone 'Station' has been converted to a networked 'Station', you
have to configure the IP address manually.
w The configuration for a ↑ 'Site' with a standalone 'Station' is loaded in
Cerberus-Engineering-Tool.
1. Select the 'Network' task card.
2. Open 'Global system configuration' > 'FS720 network configuration' > 'Ethernet
sub-net' in the tree structure.
3. Select 'Connections' to configure an Ethernet network.
Alternative for SAFEDLINK network: Select 'Ethernet sub-net'.
Select 'New element'.
Add the 'SAFEDLINK sub-net' element.
Open 'SAFEDLINK sub-net'.
Select 'Connections'.
4. In the menu bar, click on 'Assign'.
a The 'Assign dialog' window opens.
5. Select the 'Station' on the right in the Network tree and click on 'Assign'.
a The standalone 'Station' is now a networked 'Station'.
6. Select the 'Station' under 'Connections'.
7. Configure the IP address on the 'Overview' tab.
a You have converted the standalone 'Station' to a networked 'Station'.