Floor Repeater Terminal Ft2010 - Siemens FS720 Commissioning, Maintenance, Troubleshooting

Fire detection system
Table of Contents

Advertisement

Updating the firmware
22
Updating the FW of the peripheral devices

22.8.2 Floor repeater terminal FT2010

132 | 178
Building Technologies
Fire Safety
WARNING
Incorrect assignment between detector/detector zone and customer text
Misleading messages in the event of an alarm
Never change the wiring during the firmware update.
The firmware must be updated individually for each ↑ floor repeater terminal.
Preparation
w The floor repeater terminal is fed by a 24 V external power supply or by the C-
NET detector line.
w The driver for the MCL-USB adapter FDUZ221 or FDUZ227 is installed on the
PC.
1. Select 'File' > 'Import new resource package'.
2. In the selection window, open an F-FXS7211-XX_x_x_...zip file matching the
↑ 'Site'.
3. Open the device and connect the PC via the MCL-USB adapter to the device.
FT2010
X100
24 V
Figure 4: Connect the PC to the floor repeater terminal
FDUZ221 /
MCL-USB adapter (interface USB/MC-LINK)
FDUZ227
X100
Connection for the MCL-USB adapter
FT2010
Floor repeater terminal
USB
MC-Link
FDUZ221/FDUZ227
A6V10210416_j_en_--
2018-08-29