Fn2012-A1 Integrated Into Station - Siemens FS720 Commissioning, Maintenance, Troubleshooting

Fire detection system
Table of Contents

Advertisement

Commissioning Ethernet switch (modular) FN2012-A1
17

FN2012-A1 integrated into station

17.2 FN2012-A1 integrated into station
92 | 178
Building Technologies
Fire Safety
This description is for an FN2012-A1 that is connected to the station via a ribbon
cable.
You will find information on mounting and installing the FN2012-A1 in document
A6V10210390. See chapter 'Applicable documents'.
The FN2012-A1 has no IP address in the factory setting.
You will find an overview on converting a configuration in chapter 'Converting the
configuration [➙ 128]'.
You will find detailed information on converting a site to the latest market package
in document 'A6V10260976'. See chapter 'Applicable documents'
Commissioning an integrated FN2012-A1
w The FN2012-A1 is connected to the station via a ribbon cable.
w The rotary switch on the FN2012-A1 is set to '0'.
Configure the integrated Ethernet switch FN2012-A1 in the Engineering Tool.
l
You will find detailed information on configuring the Ethernet switch FN2012-A1
in document A6V10210424. See chapter 'Applicable documents'.
See also
2 Commissioning a web interface [➙ 93]
2 Converting the configuration [➙ 128]
A6V10210416_j_en_--
2018-08-29