15.8 Switch off

15.8.1 Safety during switch-off

15.8.2 Switching off the detector line

15.8.3 Switch off zone

15.9 Switching on

15.9.1 Switch on detector line

Building Technologies
Fire Safety
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
Deploy staff to monitor the deactivated area.
You must switch deactivated parts of the 'Site' back on as soon as possible.
1. Select 'Main menu' > 'Topology' > ↑ 'Hardware tree' > ↑ 'Station' > ↑ line card
> ↑ detector line.
2. Press the 'More Options' ↑ softkey and select 'Execute commands'.
3.
WARNING! System parts that have been switched off make it impossible to
acquire and process alarms or faults! Select the 'Detector line OFF' command.
a The yellow 'ISOLATION' LED lights up.
a The detector line is switched off.
1. Select 'Topology' > ↑ 'Detection tree' > ↑ 'Area' > ↑ 'Section' > ↑ 'Zone' in the
main menu.
2. Press the 'More Options' softkey and select 'Execute commands'.
3.
WARNING! System parts that have been switched off make it impossible to
acquire and process alarms or faults! Select the 'Off' command.
a The yellow 'ISOLATION' LED lights up.
a The 'Zone' is switched off.
1. Select 'Main menu' > 'Topology' > ↑ 'Hardware tree' > ↑ 'Station' > ↑ line card
> ↑ detector line.
2. Press the 'More Options' ↑ softkey and select 'Execute commands'.
3. Select the 'Detector line ON' command.
a The yellow 'ISOLATION' LED goes out.
a The detector line is switched on.
Detailed commissioning steps
Switch off
A6V10210416_j_en_--
15
79 | 178
2018-08-29