Commissioning Of I/O Card (Remote Transmission) Fci2007-A1 And I/O Card (Horn/Monitored) Fci2009-A1 - Siemens FS720 Commissioning, Maintenance, Troubleshooting

Fire detection system
Table of Contents

Advertisement

Commissioning of I/O card (remote transmission) FCI2007-A1 and I/O card (horn/monitored) FCI2009-A1

20 Commissioning of I/O card (remote
FCI2007-A1
Building Technologies
Fire Safety
transmission) FCI2007-A1 and I/O card
(horn/monitored) FCI2009-A1
With the I/O card (remote transmission) FCI2007-A1 and I/O card (horn /
monitored) FCI2009-A1, the monitored outputs are monitored for short-circuit and
open line. The resistance values of the lines may be read in and stored at the push
of a button. If a deviation from the quiescent value is detected, the control panel
evaluates a short-circuit or an open line.
The following outputs must be calibrated upon commissioning:
FCI2007-A1: 'OUT1' to 'OUT3'
FCI2009-A1: 'OUT1' to 'OUT8'
You will find more information about the FCI2007-A1 and FCI2009-A1 I/O cards
and planning monitored outputs in documents A6V10210362 and A6V10210368.
See chapter 'Applicable documents'.
S501
S501
Button
Procedure
1. Check the connected lines for short-circuit and open line.
2. Connect the lines.
a During the commissioning of the control panel, fault messages are
indicated, provided that there are any deviations from the basic settings.
3. Press the S501 button.
a The resistance values are read in.
You can also read in the resistance values via the control panel's ↑ Person
Machine Interface.
FCI2009-A1
20
S501
109 | 178
A6V10210416_j_en_--
2018-08-29