  • Page 1 Fire Alarm Control Panel Model FC2005/FC901 Programming Manual Building Technologies Fire Safety & Security Products...
  • Page 2: Table Of Contents

    Programming Manual of FC2005/FC901 TABLE OF CONTENTS INTRODUCTION ············································································································································ 2 INTERFACE ··········································································································································· 4 USER LEVEL ········································································································································· 7 2.1 Login ···················································································································································· 8 2.2 Logout ·················································································································································· 8 ALPHANUMERIC CHARACTER ENTRY ····································································································· 9 HOW TO VIEW PROPERTY ···················································································································· 10 HOW TO VIEW HISTORY ························································································································ 11 HOW TO DISABLE/ENABLE ···················································································································...
  • Page 3: Introduction

    Programming Manual of FC2005/FC901 INTRODUCTION The FC2005/FC901 Fire Alarm Control Panel can be configured on site. In FC2005/FC901 system, all system information is organized with the concept of the hardware tree, detection tree, control tree and dialer group. And the whole workflow of the system configuration and commissioning are also based on that.
  • Page 4 Programming Manual of FC2005/FC901 DACT: The Digital Alarm Communication Transmitter board which will send control panel status data to a remote receiving station. DACT Connection: DACT has two physical connections to PSTN, two telephone lines. One is the main connection and the other is used as backup connection.
  • Page 5: Interface

    Programming Manual of FC2005/FC901 1. INTERFACE Fig. 1-1 Interface of FC2005/FC901 LCD: a 160 by 64 dot LCD display is used to display event data, including alarms and troubles conditions, zone or device custom identification of messages, and a log of the system event history. A back light is included in the display to assure visibility in low light;...
  • Page 6 Programming Manual of FC2005/FC901 LED: Steady ON This indicates that the system's main power works normally. This indicates that the system is not powered on yet. This LED can Power Green be OFF only when the system is shut down.
  • Page 7 Programming Manual of FC2005/FC901 Button: Silences all silenceable devices in system. This will cause all activated Alarm Silence Press silenceable devices to become silenced. Acknowledge Press Acknowledges all unacknowledged events in system. Clears all obsolete events except those disabled ones, and deactivate all...
  • Page 8: User Level

    Programming Manual of FC2005/FC901 2. USER LEVEL The following levels of security protect the system from unauthorized use: L 1 (User) – Locked Door L 2 (Maintenance) – Locked Door and 4-digit Maintenance Password L 3 (Technician) – Locked Door and 4-digit Technical Password...
  • Page 9: Login

    Programming Manual of FC2005/FC901 2.1 Login Press “Menu” to display the main menu (Fig. 2-1). Press “ ” to select “Login” and press “OK”, the password entry screen is displayed (Fig. 2-2). Fig. 2-1 Enter the password of maintenance level or technician level and press “OK”, login successfully if the password is correct.
  • Page 10: Alphanumeric Character Entry

    Programming Manual of FC2005/FC901 ALPHANUMERIC CHARACTER ENTRY Numerals entry: Press numeral key, then the numeral is entered. Letters entry: Letters are entered using numerals key. Press down the numeral key which includes the letter (shown at the upper left corner of key), all included letters (upper case and lower case) and the numeral will be orderly and repeatedly displayed.
  • Page 11: How To View Property

    Programming Manual of FC2005/FC901 HOW TO VIEW PROPERTY Function: This feature allows user to view device property. Steps: Select an element by navigating hardware tree or detection tree (i.e., NAC) (Fig. 4-1). Fig.4-1 Press “OK” to pop out a menu (Fig. 4-2).
  • Page 12: How To View History

    Programming Manual of FC2005/FC901 HOW TO VIEW HISTORY Function: A panel includes a non-volatile memory recording 1000 system events. Identified alarm, trouble, supervisory, status and other significant events will be recorded along with the date and time of occurrence. This feature allows user to view these events.
  • Page 13: How To Disable/enable

    Programming Manual of FC2005/FC901 HOW TO DISABLE/ENABLE Function: This feature allows devices to be disabled for service. A trouble condition is annunciated whenever the disable feature is used and cleared when enabled. Note: Disabled device cannot send any message to controller.
  • Page 14: How To Activate/deactivate

    Programming Manual of FC2005/FC901 HOW TO ACTIVATE/DEACTIVATE Function: Any output (i.e., control module, NAC devices etc.) can be activated/deactivated through controller manually. Steps to activate (i.e., NAC activate): Select a device (NAC) by navigating hardware tree (Fig. 7-1). Fig.7-1 Press “Menu” to display the main menu (Fig. 7-2).
  • Page 15: How To Do Quick Test

    Programming Manual of FC2005/FC901 HOW TO DO QUICK TEST Function: To test installation quickly and easily. The installed device can be activated and NACs can be activated for a short period of time. The quick test menu allows user to configure quick test parameters. User can stop the quick test manually.
  • Page 16 Programming Manual of FC2005/FC901 Steps: Press “Menu” to display the main menu (Fig. 8-1). Press “ ” to select “Oper” submenu, press “ ” to select “Quicktest” (Fig. 8-2) and press “OK”, the quick test configure Fig. 8-1 screen is displayed (Fig. 8-3).
  • Page 17: How To Do Device Test

    Programming Manual of FC2005/FC901 HOW TO DO DEVICE TEST Function: Before doing device test on site, set device as test mode so that alarm will be released faster. Steps to device test: Select a device by navigating hardware tree (Fig. 9-1).
  • Page 18: How To Do Short Recovery/ Re-startup

    Programming Manual of FC2005/FC901 10. HOW TO DO SHORT RECOVERY/ RE-STARTUP Function: short recovery is to recover SLC line short trouble; Re-startup can be clear all events on P2 line and start up P2 line. Steps to short recovery: Short trouble is displayed (Fig. 10-1).
  • Page 19: How To Switch On/off Buzzer

    Programming Manual of FC2005/FC901 11. HOW TO SWITCH ON/OFF BUZZER Function: To turn on/off buzzer. Only user level 3 can do it. Steps: Press “Menu” to display the main menu (Fig. 11-1). Press “ ” to select “Oper” submenu (Fig. 11-2), press " " to Fig.11-1...
  • Page 20: How To Set Time

    Programming Manual of FC2005/FC901 12. HOW TO SET TIME Function: To configure the date and time of the system and display format. Steps: Press “Menu” to display the main menu (Fig.12-1). Press “ ” to select “Oper” submenu (Fig.12-2), press " " to Fig.12-1...
  • Page 21: How To Change Password

    Programming Manual of FC2005/FC901 13. HOW TO CHANGE PASSWORD Function: To change the maintenance and technician password for security. Steps: Press “Menu” to display the main menu (Fig.13-1). Press “ ” to select “Oper” submenu (Fig.13-2), press" " to Fig.13-1 select "Parameter"...
  • Page 22: How To Do Lamp Test

    Programming Manual of FC2005/FC901 14. HOW TO DO LAMP TEST Function: To check the LCD, LEDs and buzzer. When it is activated, it will turn on the LEDs, sounds the buzzer and LCD displays. User doesn't need to turn it off manually. Lamp test will automatically quit when it completes.
  • Page 23: How To Save Configure

    Programming Manual of FC2005/FC901 15. HOW TO SAVE CONFIGURE Function: To save changes permanently, otherwise the changes will be lost when the system is restarted. Steps: Press “Menu” to display the main menu (Fig.15-1). Fig.15-1 Press “ ” to select "Conf" submenu (Fig.15-2), press “OK” to display the configuration saving window (Fig.15-3).
  • Page 24: How To Edit Parameter

    Programming Manual of FC2005/FC901 16. HOW TO EDIT PARAMETER Function: To modify parameters of device and panels. See Appendix table 1 for parameters details. Steps: To Select an element (i.e., NAC1) by navigating hardware tree or detection tree (Fig.16-1). Press “OK” to pop out a menu (Fig.16-2).
  • Page 25: How To Create/delete Logic Control

    Programming Manual of FC2005/FC901 17. HOW TO CREATE/DELETE LOGIC CONTROL Function: To create/delete logic control among detection group, supervision group and control output group. Steps of creating: Press “Menu” to display the main menu (Fig.17-1). Press “ ” to select “Control” item and press “OK” (Fig.17-2), Fig.17-1...
  • Page 26 Programming Manual of FC2005/FC901 Steps of deleting: To select a logic control which need to be deleted, press” Menu” and press “ ” to select “Conf” submenu, to select “Delete” and press “OK” (Fig. 17-11), deleting confirming screen is displayed (Fig.
  • Page 27: How To Edit Logic Control

    Programming Manual of FC2005/FC901 18. HOW TO EDIT LOGIC CONTROL Function: To edit logic control. Steps: Press “Menu” to dispaly the main menu (Fig.18-1). Fig.18-1 Press “ ” to select “Control” item (Fig.18-2) and press “OK”, all logic expressions are listed (Fig.18-3) .
  • Page 28 Programming Manual of FC2005/FC901 Fig.18-7 Fig.18-8 Fig.18-9 Page: 27/48...
  • Page 29: How To Create/delete Dialer Group

    Programming Manual of FC2005/FC901 19. HOW TO CREATE/DELETE DIALER GROUP Function: The intend of DialerGroup is to reduce messages reported to supervising station. e.g. If two zones both detected alarm condition but they are close to each other, sending one piece of alarm message to inform the supervising station will be enough.
  • Page 30 Programming Manual of FC2005/FC901 To select “Confirm” and press “OK”, the new dialer group is created and shown (Fig.19-9). Fig.19-6 Steps of deleting: To select a dialer group which need to be deleted, press” Menu” and press “ ” to select “Conf” submenu, to select “Delete” and press “OK”...
  • Page 31: How To Assign

    Programming Manual of FC2005/FC901 20. HOW TO ASSIGN Function: To assign a channel to a zone for logic control; To assign a zone to cause (OR) for logic control. Steps to assign a zone to cause (OR): Press “Menu” to display the main menu (Fig. 20-1).
  • Page 32: How To Get System Version

    Programming Manual of FC2005/FC901 21. HOW TO GET SYSTEM VERSION Function: To show system edition, download time of configuration file and modification time. Steps: Press “Menu” to display the main menu, press “ ” to select “About” item (Fig. 21-1).
  • Page 33: How To Set System Timer

    Programming Manual of FC2005/FC901 22. HOW TO SET SYSTEM TIMER Function: This option allows the user to set the following system timer parameters: Timer Description Value Scope Default Min. Step Reset Inhibit Sets the time the user is prevented form {min:0;max:6;}...
  • Page 34 Programming Manual of FC2005/FC901 or not. Set if the status events can be removed from event list after it disappears. If it is set as False, Status Self a Status Restoral event will be created and {True;False;} True Restoring appended in event list on the event disappears.
  • Page 35: How To Configure A New System

    Programming Manual of FC2005/FC901 23. HOW TO CONFIGURE A NEW SYSTEM After all of the devices, notification appliances and option modules have been installed, check all wiring for grounds, shorts and opens. Confirm all wirings are security and switch power on. Panel will recognized all connected devices and show them under hardware tree.
  • Page 36: Appendix 1 Parameter List

    Programming Manual of FC2005/FC901 APPENDIX 1 PARAMETER LIST Equipment type Editable item Parameter description Panel Name Name of panel which will be displayed - FC2005/FC901 Buzzer Option 1: On (default) Option 2: Off Maintenance Default: 1234 Password Technician Password Default: 4321...
  • Page 37 Programming Manual of FC2005/FC901 Relays on board Silenceable Bool: True (default)/ False HoldThroughReset Bool: True/ False (default) Wire Style Option 1: Class A NAC loop Option 2: Class B(default) Option 1: Strobe (default) Device Type Option 2: Audible Option 3: Strobe/audible Only when device type is audible, the follow options are available.
  • Page 38 Programming Manual of FC2005/FC901 HoldThroughReset Bool: True/ False (default) (output channel) 8705 Name Address LED normal off Bool: True/ False (default) Alarm Verification Bool: True/ False (default) (channel) 8706 Name Address Silenceable Bool: True (default)/ False (channel) HoldThroughReset Bool: True/ False (default)
  • Page 39 Programming Manual of FC2005/FC901 8726 Name Address Silenceable Bool: True (default)/ False (channel) HoldThroughReset Bool: True/ False (default) (channel) OOH941 Name Address LED normal off Bool: True/ False (default) Multi Critieria Usage Option 1: ASD (default) (channel) Option 2: Photoelectric(alarm)
  • Page 40 Programming Manual of FC2005/FC901 ASD Setting Option 1: Telecommunication Option 2: Incipient Option 3: Ion equivalent Option 4: Data Center Option 5: Computer Room Option 6: Precious Storage Option 7: Power Generation Option 8: Hospital Option 9: Health Care Option 10: Dormitory...
  • Page 41 Programming Manual of FC2005/FC901 ASD Setting Option 1: Telecommunication Option 2: Incipient Option 3: Ion equivalent Option 4: Data Center Option 5: Computer Room Option 6: Precious Storage Option 7: Power Generation Option 8: Hospital Option 9: Health Care Option 10: Dormitory...
  • Page 42 Programming Manual of FC2005/FC901 ASD Setting Option 1: Telecommunication Option 2: Incipient Option 3: Ion equivalent Option 4: Data Center Option 5: Computer Room Option 6: Precious Storage Option 7: Power Generation Option 8: Hospital Option 9: Health Care Option 10: Dormitory...
  • Page 43 Programming Manual of FC2005/FC901 Sensoractivationdelay Option 1: 0.25s(default) (input channel) Option 2: 0.5s Option 3: 1s Option 2: 2.5s Option 4: 5s Option 5: 10s Option 6: 20s Option 7: 45s Option 8: 60s Option 9: 90s Option 10: 120s...
  • Page 44 Programming Manual of FC2005/FC901 Thermal Alarm Setting Option 1: Fixed temperature 135°F (channel) Option 2: Fixed temperature 135°F + ROR 15°F FDO421 Name Address LED normal off Bool: True/ False (default) Sensitivity Option 1: Sensitive 1.40%/ft (channel) Option 2: Standard 1.80%/ft Option 3: Robust 2.30%/ft(default)
  • Page 45 Programming Manual of FC2005/FC901 ASD Setting Option 1: Off (default) (channel) Option 2: Office/Retail Option 3: Warehouse Option 4: Lobby Option 5: Computer Room Option 6: Dormitory Option 7: Health Care Option 8: Parking Garage Option 9: Equip Storage/Transformer Room...
  • Page 46 Programming Manual of FC2005/FC901 Normally Open Bool: True (default)/ False (channel) HTRI-R Name Address LED normal off Bool: True/ False (default) Normally Open Bool: True (default)/ False (input channel) Silenceable Bool: True (default)/ False (output channel) HoldThroughReset Bool: True/ False (default)
  • Page 47 Programming Manual of FC2005/FC901 Option 2: Can Option 3: Must Not Option 1: Must (default) Report Trouble Option 2: Can Restoral Option 3: Must Not Option 1: Must (default) Report Supervisory Option 2: Can Restoral Option 3: Must Not Report Test...
  • Page 48 Programming Manual of FC2005/FC901 Adv. Control 1 Name Effect Min:0; Max:180 ActivationDelay (Under Advanced. Default value is 0. control) Min: 0; Max:180 DeactivationDelay Default value is 0. Ignore Reset Bool: True/ False (default) Command Option 1: Alarm(default) Option 2: Trouble...
  • Page 49: Appendix 2 Trouble-shooting

    Status: FXS901-U2/U3 reports Version Mismatch when user performs download Firmware or Configuration or upload Configuration. Possible Causes: The sales channel of FXS901-U2/U3 and FC2005/FC901 is incompatible. You can not use FXS901-U2 to communicate with FC901 and vice versa. Handling: Find a compatible version FXS901-U2/U3 and try again.
  • Page 50 © 2011 Copyright by Beijing Siemens Cerberus Electronics Limited No.1,Fengzhidonglu, Xibeiwang, HaiDian District, Beijing Siemens Cerberus Electronics Ltd. Beijing, 100094, China Data and design subject to change without notice. Tel: +10 6476 8806 Fax: +10 6476 8899 Doc. No. A6V10333724_a_en_--...