Limitations Of C-Bus Participants; Main Cpu Limits; Maximum Number Of Devices; Limits In The Logical Structure - Siemens FC700A System Planning Manual

Fire detection system
Table of Contents

Advertisement

Limitations of C-Bus participants

8
Limitations of C-Bus participants
Station type
FC700A
FT700A
FG700A
8.1

Main CPU limits

8.1.1

Maximum number of devices

8.1.2

Limits in the logical structure

8.1.3

Maximum number of criteria in zones control 4 and 6

8.1.4

Maximum number of ZONE time channel

20
Siemens Building Technologies
Fire & Security Products
This chapter describes the quantitative limits of the FC700A station.
The selection of the station type depends on the requirements. The following vari-
ants are available:
Flash ROM
Modules
(2x1024Kx8Bit)
'Program file'
B3Q700
CIY00760
B3Q700
CTY00760
E3H020
1000 devices (with AMPK=1) per FC700A.
The limits in the logical structure are given by the node-type, by the highest possi-
ble CSX number and the maximum amount of display-digits. These limits are given
by the system and are independent of the memory capacity.
Table 'Limits of the logical structure'
Maximum rating
AREAS per STATION
... 4
The maximum number of control zones with 16 criteria is limited by 200.
To optimize the performance of your system minimize the number of CPU-overlapping controls as
much as possible.
A maximum of 40 CPU-overlapping controls (zone control 6) are admissible per C-Bus.
Max. 16 ZONES time channel are permitted per station.
SRAM
Soldered
4x512Kx8Bit
4x512Kx8Bit
Maximum rating
Maximum rating
SECTIONS per AREA
ZONES per SECTION
...255
EPROM set
RAM set
2 x Z3S070
CKQ007.60
(2x512Kx8Bit)
(2x512Kx8Bit)
(Assembly ex works)
Maximum rating
ELEMENTS per ZONE
...255
...99
International 5: ...255
007836_a_en_--.doc