22.8.6 Line tester FDUL221

Building Technologies
Fire Safety
This chapter relates to the line tester FDUL221, device version with USB
connection or MC link connection, order no. A5Q00022100.
Preparation
1. Save the latest firmware file on your PC.
2. Select 'File' > 'Import new resource package' in the Engineering Tool.
3. In the selection window, open the firmware file with the corresponding
language F-FXS2007-XX_x_x_...zip.
Connection to PC via USB cable
w The line tester is fed either internally with batteries or via a mains adapter.
Connect the device to the PC via the USB cable. You will find more information
l
in document 008250. See chapter 'Applicable documents'.
Connection to PC via FDUZ22x
w The driver for the MCL-USB adapter FDUZ221 or FDUZ227 is installed on the
PC.
w The line tester is fed either internally with batteries or via a mains adapter.
Connect the device to the PC via the MCL-USB adapter. You will find more
l
information in document 008250. See chapter 'Applicable documents'.
FDUL221
Figure 7: Connect the PC to the line tester
FDUZ221 /
MCL-USB adapter (interface USB/MC-LINK)
FDUZ227
FDUL221
Line tester
DC
Supply with network adapter DC 24 V / 625 mA
B
Battery compartment 2 x 9 V
If the device has no MC link connection, it is an older device version with an
RS232 connection. You will find more information on this in the next chapter.
Updating the FW of the peripheral devices
USB
DC
FDUZ221/FDUZ227
MC-Link
Updating the firmware
22
139 | 178
A6V10210416_j_en_--