Commissioning overview
5
Commissioning variants
5 Commissioning overview
5.1 Commissioning variants
Without
No pre-
Cerberus-
configuration
Engineering-
possible
Tool
With
Without pre-
Cerberus-
configuration
Engineering-
Tool
With pre-
configuration
34 | 178
Building Technologies
Fire Safety
The 'Stations' on the C-WEB, such as control panels FC722/FC724 and fire
terminals FT724, are connected to the power supply and commissioned by the
installation and commissioning personnel.
●
Networked 'Stations' must only be commissioned with Cerberus-Engineering-
Tool.
●
Standalone control panels can be commissioned with or without Cerberus-
Engineering-Tool.
NOTICE
Impermissible commissioning procedures result in faults during operation.
●
Only the procedures described in this document are permitted.
NOTICE
Not the current firmware version status of a newly installed fire detection
installation
Possible limitations for the configuration or use of devices.
●
Compare the firmware version of a newly installed fire detection installation
with the currently approved firmware version status.
●
Use the currently approved firmware version status.
●
Update the firmware if required, in accordance with the chapter 'FW update
for main CPU and additional CPUs' in document A6V10210416; see chapter
'Applicable documents'.
The table below provides an overview of the procedure for commissioning the
'Stations'. The letters A, B1, B2 and C refer to the detailed descriptions in the
following chapters.
Standalone control panel
A
●
↑ Auto-configuration
●
Adaptations on the ↑ Person
Machine Interface
B1
●
Auto-configuration
●
Adaptations in Cerberus-
Engineering-Tool
B2
●
Read in the FDnet devices by line
●
Assign the logical elements to
Cerberus-Engineering-Tool
Table 1: Commissioning variants
Networked 'Stations'
Not possible.
C
●
Initialize the 'Stations' for
networking
●
Read in the C-NET devices by line
●
Assign the logical elements to
Cerberus-Engineering-Tool
A6V10210416_j_en_--
2018-08-29