Siemens FS720 Commissioning, Maintenance, Troubleshooting page 65

Fire detection system
Table of Contents

Advertisement

Entry in the calibration
report
10th to max. 252nd
Voltage drop on the
individual 'Voice alarm
sounder beacon/Voice al.
sound. beacon base'
devices on the line
Building Technologies
Fire Safety
Possible content*
FDS227 - RR
Device 1/2/1/1 PASS U = 23.4 V
FDS227 - RR
Device 1/2/1/1 FAIL U = 15.7 V
* The specified lines, devices, and values are only examples.
Calibrating an FDnet/C-NET detector line
Calibration report
Description
Entries 10 to max. 252 show the
calculated voltage drop on each 'Voice
alarm sounder beacon/Voice al. sound.
beacon base' device in the line.
The following results are possible:
Pass: The calculated operating
voltage for the 'Voice alarm sounder
beacon/Voice al. sound. beacon
base' device in question is ≥ 16 V
for devices with beacon and ≥ 12 V
for devices without beacon.
Fail: The calculated operating
voltage for the 'Voice alarm sounder
beacon/Voice al. sound. beacon
base' device in question is < 16 V
for devices with beacon and < 12 V
for devices without beacon.
13
65 | 178
A6V10210416_j_en_--
2018-08-29