Updating the firmware
22

Updating the FW of Ethernet switch (modular) FN2012-A1

22.9 Updating the FW of Ethernet switch (modular)

22.9.1 Standalone FN2012-A1

142 | 178
Building Technologies
Fire Safety
4. Press and hold down the '▲', '▼', and '√' buttons on the line tester and click on
the 'Next' button in the Engineering Tool at the same time.
5. Only release the '√' button.
a The device is set to update mode.
6. Release the '▲' and '▼' buttons.
7. Follow the instructions in the dialog in the Engineering Tool and perform the
update.
a The line tester restarts.
8. Remove the MCL-USB adapter.
a The firmware is updated.
FN2012-A1
See also
2 Commissioning Ethernet switch (modular) FN2012-A1 [➙
90]
'Cerberus-Engineering-Tool' assumes the function of the TFTP server from which
the FN2012-A1 obtains the firmware. The FN2012-A1 must be connected to a sub-
net containing at least one station that can provide the PC with the DHCP.
You can perform the firmware update for the FN2012-A1 in two ways:
Updating the firmware in the web interface
or
Updating the firmware with the RESET button on the device
The web interface is not available while the firmware update is active.
A6V10210416_j_en_--
2018-08-29