Addressable Detectors; Fs-Dpt Photoelectric Detector With Thermal; Fs-Dt Thermal Detector; Fs-Dp Photoelectric Detector - Siemens FireSeeker FS-100 Installation, Operation And Maintenance Manual

Hide thumbs Also See for FireSeeker FS-100:
Table of Contents

Advertisement

FS-100 Installation & Operation Manual

Addressable Detectors

Each detector uses an address between 01 and 60 on the addressable device circuit.
All device
addresses are programmed into the device using the FS-DPI Device Programmer Unit. When installed,
the device is regularly scanned by the control unit and checked for its current sensor status. The control
unit will interpret and respond to the analog data as programmed. Each time the device is scanned the
integral green visible LEDs will flash. In the event of an alarm condition the red LEDs will flash at a faster
rate.

FS-DPT Photoelectric Detector with Thermal

The FS-DPT Photo/Thermal Detector allows programmable analog sensitivity with fixed thermal
temperature of 135° F. It requires a DB-11, DB-X11RS, ADBX-11, AD-11P, or ADX-11PR base.

FS-DT Thermal Detector

The FS-DT Thermal Detector is a fixed 135° F detector. It requires a DB-11, DB-X11RS, ADBX-11, AD-
11P, or ADX-11PR base.

FS-DP Photoelectric Detector

The FS-DP Photoelectric Detector allows programmable analog sensitivity. It requires a DB-11, DB-
X11RS, ADBX-11, AD-11P, or ADX-11PR base.

DB-11, ADBX-11 and DBX-11RS Detector Bases

The DB-11 base is a standard base designed for use with all FS-Series addressable and all 11-Series
conventional detectors. The DB-11 provides connection to an optional remote LED lamp (RLI-1 or RLI-2
lamp).
The ADBX-11 audible detector base is designed for use with all FS-Series addressable detectors. The
ADBX-11 provides means to obtain a local audible alarm at the specific detector location. The integral
horn on the ADBX-11 will sound when either the detector installed in the base has latched into the alarm
state, or when criteria developed through logic programming is met. It will remain on until the detector is
successfully reset, or the logic criteria are no longer met. A separate 24VDC power source is required to
operate the integral horn.
The DBX-11RS relay detector base is designed for use with all FS-Series addressable detectors. The
DBX-11RS provides a local Form C relay at the specific detector location. The relay on the DBX-11RS
will energize when either the detector installed in the base has latched in the alarm state, or when criteria
developed through logic programming is met. It will remain energized until the detector is successfully
reset, or the logic criteria are no longer met. The contact is rated at 3A, 120VAC, or 3A, 30VDC resistive.

AD-11P and ADX-11PR Air Duct Housing

The AD-11P Air Duct Housing and the ADX-11PR Air Duct Housing are used with the FS-DP addressable
photo detector. Both housings provide a means to mount the FS-DP in an air duct for proper operation of
the detector in an air stream. The ADX-11PR also has an integral Form C contact that operates similarly
to the DBX-11RS relay base.

LIM-1 Line Isolator Module

The LIM-1 Line Isolator Module is designed for use with FS-Series addressable detectors and provides
short circuit isolation on the indicating device circuit. Each LIM-1 can support up to 20 devices. The
system is limited to 12 LIM-1s on the circuit.
33
P/N 315-699461