Commissioning security module (firewall) FN2009-A1
18
Creating IP service definitions
18.4 Creating IP service definitions
104 | 178
Building Technologies
Fire Safety
NOTICE
Different ↑ BACnet port settings in FN2009-A1 and Cerberus-Engineering-Tool
No communication possible
●
Configure the same BACnet port in FN2009-A1 and Cerberus-Engineering-
Tool.
1. Open the 'Options' > 'IP Service Definitions' menu.
a The 'IP Service Definitions' window is opened.
2. Select the 'IP Services' tab.
3. Click on 'Add IP Service'.
a One row can be edited for one IP service.
4. Enter the two IP services required as shown in the figure above:
–
'Name': Tool, 'Protocol': udp, 'Source Port': *, 'Target Port': 51000
–
'Name': BACnet, 'Protocol': udp, 'Source Port': *, 'Target Port': 47808
a Required IP services are created.
5. Select the 'ICMP' tab.
6. Click on 'Add ICMP Service'.
a One row can be edited for one ICMP service.
A6V10210416_j_en_--