Switch On Zone; Restarting The Detector Line - Siemens FS720 Commissioning, Maintenance, Troubleshooting

Fire detection system
Table of Contents

Advertisement

Detailed commissioning steps
15

Restarting the detector line

15.9.2 Switch on zone

15.10 Restarting the detector line
80 | 178
Building Technologies
Fire Safety
1. Select 'Topology' > ↑ 'Detection tree' > ↑ 'Area' > ↑ 'Section' > ↑ 'Zone' in the
main menu.
2. Press the 'More Options' softkey and select 'Execute commands'.
3. Select the 'On' command.
a The yellow 'ISOLATION' LED goes out.
a The 'Zone' is switched on.
WARNING
Activation of fire or smoke dampers
If fire or smoke dampers are connected to the FS720 via an input/output module,
they may be activated when the station is switched off or when the station or
detector line is restarted.
If necessary, block the outputs temporarily [➙ 81] before switching off the
station or restarting the station/detector line.
1. Select 'Main menu' > 'Topology' > ↑ 'Hardware tree' > ↑ 'Station' > 'Module'
(line card) > 'Line'.
2. Press the 'More Options' ↑ softkey and select 'Execute commands'.
3. Select the 'Restart line' command.
a The ↑ detector line is restarted. The following messages are displayed:
'Line starting up'
'Device config.runs'
Start line test
Only test the line and line devices once the following messages have disappeared
from the PMI:
- 'Device config.runs'
- 'System startup completed'
A6V10210416_j_en_--
2018-08-29