Testing The 'Station - Siemens FS720 Commissioning, Maintenance, Troubleshooting

Fire detection system
Table of Contents

Advertisement

23.6 Testing the 'Station'

Building Technologies
Fire Safety
Check the hardware
Check the condition of the housing and the components.
Check the fixture of screws, terminals and plug connections.
Check that the batteries are not leaking (inspection).
Check labeling
Check that the inscription strips are correct and still easily legible.
Check the function
1. Enter the password.
2. Initiate the lamp test.
3. Check switchover of operation modes from 'Manned operation' to 'Unmanned
operation' and vice versa.
4. Switch an 'Area' off and on again.
5. Check the operation of an alarm.
6. Check the operation of a 'Fault'.
7. Block operation.
Clean the operating unit
Clean the display and the front plate with a wet cloth. Do not use any caustic
solvents.
Maintenance
23
Testing the 'Station'
149 | 178
A6V10210416_j_en_--