Base Without Loop Contact - Siemens FS720 Commissioning, Maintenance, Troubleshooting

Fire detection system
Table of Contents

Advertisement

12.4.1.3 Replacing non-stationary devices of different types

12.4.2 Base without loop contact

Building Technologies
Fire Safety
Changing and expanding the FDnet/C-NET detector line
You will find additional information about the individual steps on the specified
pages.
1. Remove the C-NET device from its base.
a The ↑ 'Station' detects that the device is missing and reports a 'Fault'.
2. Delete the C-NET device on the ↑ Person Machine Interface on the control
panel. Link [➙ 83]
3. Insert the new C-NET device in the base.
4. Read-in the C-NET devices. Link [➙ 82]
5. Connect the PC to the 'Station'. Link [➙ 27]
6. Load the configuration from the 'Station' to the PC. Link [➙ 32]
7. Replace the C-NET device in the 'Zone'. Link [➙ 51]
8. Load the configuration from the PC to the 'Station'. Link [➙ 30]
9. Disconnect the PC from the 'Station'. Link [➙ 27]
The work described in this chapter may be performed when the C-NET detector
line is switched on.
Replacing a device in the 'Zone'
1. Select the 'Zone' in which you have replaced a device in Cerberus-
Engineering-Tool. The 'Find' or 'Find and replace' functions can be used to do
this.
2. Replace the C-NET device.
You will find more information in document A6V10210424. See chapter 'Applicable
documents'.
If a C-NET device is removed, the detector line is interrupted from this point. If the
device is on a stub or sub-stub, communication between the control panel and
downstream devices is interrupted. These devices are shown as missing on the
control panel.
The work described in this chapter may only be performed when the C-NET
detector line is switched off.
Removing or replacing non-stationary devices
12
51 | 178
A6V10210416_j_en_--
2018-08-29