Programming Switch "S3 - Siemens FC700A Hardware Description

Fire detection system
Table of Contents

Advertisement

7.6

Programming switch "S3"

7.7
Floating charge voltage as a function of temperature
Siemens Building Technologies
Fire & Security Products
To set I-Bus address. Each element (module) connected to the I-Bus must have an
individual address (number). This is set on programming switch "S3". Maximum 16
I-Bus users.
Function / I-Bus address
No.
0
Module out of commission (unused)
1
I-Bus user number
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
"S3-1...6" are set to "off" at the factory
The I-Bus address setting is given as default by the tool (SWE700A) as address 16, therefore the
programming switch 'S3' of the E3C011 must be set accordingly.
Programming switch S3
S3-1
off
1
on
2
off
3
on
4
off
5
on
6
off
7
on
8
off
9
on
10
off
11
on
12
off
13
on
14
off
15
on
16
off
E3C011 Battery charging module
S3-2
S3-3
S3-4
S3-5
off
off
off
off
off
off
off
off
on
off
off
off
on
off
off
off
off
on
off
off
off
on
off
off
on
on
off
off
on
on
off
off
off
off
on
off
off
off
on
off
on
off
on
off
on
off
on
off
off
on
on
off
off
on
on
off
on
on
on
off
on
on
on
off
off
off
off
on
007831_a_en_--.doc
S3-6
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
25
03.2004