Commissioning - Siemens FDOOT221 Technical Manual

Automatic fire detectors
Hide thumbs Also See for FDOOT221:
Table of Contents

Advertisement

6

Commissioning

6 Commissioning
108
Building Technologies
Fire Safety
Commissioning FDnet, AnalogPLUS and SIGMALOOP
The control panel is used to commission the detectors. The exact procedure is
described in the control panel documentation.
Migrating existing detectors
You will find further information about migration and modernization in document
A6V10323158.
Commissioning a collective or MS8 detector line
The commissioning of the collective detector line is performed on the control panel.
The exact procedure is described in the control panel documentation.
After commissioning the detector line, the parameter sets can be set with the
detector exchanger and tester FDUD292.
Changing over from collective to FDnet
When changing from a collective detector line with FD20 detectors to an FDnet
detector line, the following must be taken into account:
There is no need to exchange the detector base FDB201 by a detector base
FDB221.
It is not necessary to replace the sounder base FDSB292, either. On an FDnet
detector line the sounder base FDSB292 behaves in the same way as the
sounder base FDSB291 with product version ES 30.
When a detector is removed from an FDnet detector line and that detector is
located on a collective detector base (FDB201 or FDSB292), the
communication between the control panel and the next detector is interrupted.
In this case, alarming by the subsequent detectors is no longer possible. A fault
is indicated on the control panel.
The changeover must take place by reading in the line several times. Repeat
the reading-in process until the correct number of installed detectors per line is
read in.
Recommendation: Use the line tester FDUL221 for the changeover.