Actual Config (Actual Slave Configuration) - Pepperl+Fuchs VBG-EN-K30-DMD-S16 Manual

Ethernet/ip gateway with integrated safety monitor
Table of Contents

Advertisement

9.6.11

ACTUAL CONFIG (actual slave configuration)

Main menu || DIAGNOSIS || ACTUAL CONFIG ||
This function displays the status of the actual configuration of the individual AS-i
slaves.
A help appears at the end of the list explaining the abbreviations:
D (Detected Only): An AS-i slave is detected at this address, but it was not
P (Projected Only): An AS-i slave was designed in at this address, but it was not
C (Type Conflict): The configuration data for the detected AS-i slave do not
F (Periph. Fault): The AS-i slave has a peripheral error.
A (Duplicate Adr.): Two AS-i slaves at the indicated address.
After selecting the desired AS-i slave address, the values for the current configu-
ration data are displayed after the respective address in the following order:
IO (I/O-Configuration)
ID (ID-Configuration)
xID1 (extended ID1)
xID2 (extended ID2).
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91
ACTUAL CONFIG
0A
....
30A-X
....
30A
HELP:
X O.K.
D DETECTED ONLY
UNKNOWN SLAVE
P PROJ. ONLY
MISSING SLAVE
C TYPE CONFLICT
F PERIPH. FAULT
A DUPLICATE ADDR
X (O.K.): The configuration data for the detected AS-i slave agree with
the designed in configuration data.
designed in.
detected.
agree with the designed in configuration data. The actual exist-
ing configuration of the connected AS-i slave is displayed.
Operation in advanced display mode
|
1A-C
| 31A-D
|
1B-X
| 31B-F
© Pepperl+Fuchs, Printed in Germany
Internet http://www.pepperl-fuchs.com
AS-Interface
97