5.

Installation

5.1

Dimensions

Warning!
Cover the top of the gateway when doing any drilling work above the unit. No particles,
especially metal chips, should be allowed to enter the housing, since this could cause a
short circuit.
Information!
Please refer to installation instruction for this device for detailed mounting information.
5.2

Connections

5 ... 6 mm / PZ2
10
10
AWG
Attention!
The AS-I power supply for the AS-I components must have isolation per IEC 60 742
and be able to handle momentary power interruptions of up to 20 ms. The power sup-
ply for the 24 V supply must also have isolation per IEC 60 742 and be able to handle
momentary power interruptions of up to 20 ms. The maximum output voltage of the
power supply must also be less than 42 V in case of a fault.
22
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91
AS-i 3.0 EtherNet/IP Gateway with integrated Safety Monitor
78
96
110
0,8 Nm
7 LB.IN
2 x (0,5 .. . . 1,5) mm
2 x (0,5 .. . . 1,5) mm
2 x 24 ...12
120
2
2
Installation
© Pepperl+Fuchs, Printed in Germany
Internet http://www.pepperl-fuchs.com